Certification according to EN62208

IP RATING EN60529

CC ENCLOSURES WITH BLIND DOOR
IP66
CC ENCLOSURES WITH DOUBLE BLIND DOOR
IP55
CL ENCLOSURES WITH LEXAN DOOR
IP66
CH HYGENIC DESIGN ENCLOSURES
IP66
SC JUNCTION BOXES
IP66
MC MODULAR FLOOR-STANDING ENCLOSURES WITH BLIND DOOR
IP66
MC MODULAR FLOOR-STANDING ENCLOSURES WITH DOUBLE BLIND DOOR
IP55
ML MODULAR FLOOR-STANDING ENCLOSURES WITH LEXAN DOOR
IP66
FC COMPACT FLOOR-STANDING ENCLOSURES WITH BLIND DOOR
IP66
FC COMPACT FLOOR-STANDING ENCLOSURES WITH DOUBLE BLIND DOOR
IP55
RC COMPACT FLOOR-STANDING ENCLOSURES WITH REMOVABLE SIDES AND BLIND DOOR
IP66
RC COMPACT FLOOR-STANDING ENCLOSURES WITH REMOVABLE SIDES AND DOUBLE BLIND DOOR
IP55

 

FIRST DIGIT
protection against solid objects
SECOND DIGIT
protection against liquids
0   No protection 0   No protection
1 Protection against entry by solid objects greater than 50mm in diameter 1 Protection against dripping water (vertically falling drops)
2 Protection against entry by solid objects greater than 12mm in diameter 2 Protection against water droplets deflected up to 15° from vertical
3 Protection against entry by solid objects with a diameter or thickness of 2.5 mm or more 3 Protection against water droplets deflected up to 60° from vertical
4 Protection against entry by solid objects with a diameter or thickness of 1.0 mm or more 4 Protected against water spray from all directions
5 Protected against dust 5 Protection against low pressure water jets (all directions)
6 Totally dust tight 6 Protection against string water jets and waves
      7 Protected against temporary immersion
      8 Protected against prolonged effects of immersion under pressure

RESISTANCE TO EXTERNAL MECHANICAL IMPACT (IK) EN 62262

CC ENCLOSURES WITH BLIND DOOR
IK10
CC ENCLOSURES WITH DOUBLE BLIND DOOR
IK10
CL ENCLOSURES WITH LEXAN DOOR
IK10
CH HYGENIC DESIGN ENCLOSURES
IK10
SC JUNCTION BOXES
IK08
MC MODULAR FLOOR-STANDING ENCLOSURES WITH BLIND DOOR
IK10
MC MODULAR FLOOR-STANDING ENCLOSURES WITH DOUBLE BLIND DOOR
IK10
ML MODULAR FLOOR-STANDING ENCLOSURES WITH LEXAN DOOR
IK10
FC COMPACT FLOOR-STANDING ENCLOSURES WITH BLIND DOOR
IK10
FC COMPACT FLOOR-STANDING ENCLOSURES WITH DOUBLE BLIND DOOR
IK10
RC COMPACT FLOOR-STANDING ENCLOSURES WITH REMOVABLE SIDES AND BLIND DOOR
IK10
RC COMPACT FLOOR-STANDING ENCLOSURES WITH REMOVABLE SIDES AND DOUBLE BLIND DOOR
IK10

 

IK 0   No protection
IK 01 Protection against impact energy up to 0,150 J
IK 02 Protection against impact energy up to 0,200 J
IK 03 Protection against impact energy up to 0,350 J
IK 04 Protection against impact energy up to 0,500 J
IK 05 Protection against impact energy up to 0,700 J
IK 06 Protection against impact energy up to 1,00 J
IK 07 Protection against impact energy up to 2,00 J
IK 08 Protection against impact energy up to 5,00 J
IK 09 Protection against impact energy up to 10,00 J
IK 10 Protection against impact energy up to 20,00 J

NEMA enclosure types

NORM UL508A – CSA C22.2 n°. 14-13

 
CC ENCLOSURES WITH BLIND DOOR
NEMA 1,12,4,4X
CC ENCLOSURES WITH DOUBLE BLIND DOOR
NEMA 1,12
CL ENCLOSURES WITH LEXAN DOOR
NEMA 1,12,4,4X
CH HYGIENIC DESIGN ENCLOSURES
NEMA 1,12,4,4X
SC JUNCTION BOXES
NEMA 1,12,4,4X
MC MODULAR FLOOR-STANDING ENCLOSURES WITH BLIND DOOR
NEMA 1,12,4,4X
MC MODULAR FLOOR-STANDING ENCLOSURES WITH DOUBLE BLIND DOOR
NEMA 1,12
ML MODULAR FLOOR-STANDING ENCLOSURES WITH LEXAN DOOR
NEMA 1,12,4,4X
FC COMPACT FLOOR-STANDING ENCLOSURES WITH BLIND DOOR
NEMA 1,12,4,4X
FC COMPACT FLOOR-STANDING ENCLOSURES WITH DOUBLE BLIND DOOR
NEMA 1,12
RC COMPACT FLOOR-STANDING ENCLOSURES WITH REMOVABLE SIDES AND BLIND DOOR
NEMA 1,12,4,4X
RC COMPACT FLOOR-STANDING ENCLOSURES WITH REMOVABLE SIDES AND DOUBLE BLIND DOOR
NEMA 1,12

 

TYPE DESCRIPTION
1 Intended primarily for indoor use to provide a degree of protection against
limited amounts of falling dirt.
2 Intended primarily for indoor use to provide a degree of protection against
limited amounts of falling dirt and water.
3 Intended primarily for outdoor use to provide a degree of protection
against windblown dust, rain and sleet; undamaged by ice which forms on
the enclosure.
3R Intended primarily for outdoor use to provide a degree of protection
against rain and sleet; undamaged by ice which forms on the enclosure.
3S Intended primarily for outdoor use to provide a degree of protection
against windblown dust, rain and sleet; furthermore external mechanism
remain operable when ice laden.
4 Intended primarily for indoor and outdoor use to provide a degree of pro-
tection against corrosion, windblown dust and rain, splashing water, and
hose-directed water; undamaged by ice which forms on the enclosure.
4X Intended primarily for indoor and outdoor use to provide a degree of pro-
tection against windblown dust and rain, splashing water, and
hose-directed water; undamaged by ice which forms on the enclosure.
5 Intended primarily for indoor use to provide a degree of protection against
windblown dust, falling dirt and dripping non-corrosive liquids.
6 Intended primarily for indoor and outdoor use to provide a degree of
protection against hose-directed water and the ingress of water during
occasional, temporary submersion at a limited depth; undamaged by ice
which forms on the enclosure.
6P Intended primarily for indoor and outdoor use to provide a degree of
protection against hose-directed water and the ingress of water during
prolonged submersion at a limited depth; undamaged by ice which forms
on the enclosure.
12, 12K Intended primarily for indoor use to provide a degree of protection against
circulating dust, falling dirt and dripping non-corrosive liquids.
13 Intended primarily for indoor use to provide a degree of protection against
dust and splashes of water, oil and non-corrosive coolant.

ATEX certification

ATEX 2014/34/EU DIRECTIVE

CC ENCLOSURES WITH BLIND DOOR
EX II 3GD
CH HYGENIC DESIGN ENCLOSURES
EX II 3GD
SC JUNCTION BOXES
EX II 3GD
MC MODULAR FLOOR-STANDING ENCLOSURES WITH BLIND DOOR
EX II 3GD
ML MODULAR FLOOR-STANDING ENCLOSURES WITH LEXAN DOOR
EX II 3GD
FC COMPACT FLOOR-STANDING ENCLOSURES WITH BLIND DOOR
EX II 3GD
RC COMPACT FLOOR-STANDING ENCLOSURES WITH REMOVABLE SIDES AND BLIND DOOR
EX II 3GD

 

CATEGORY LEVEL LEVEL OF PROTECTION (Anex I) CONSTRUCTION CHARACTERISTICS (Anex II) APPLICABLE SAFETY REQUIREMENTS PRESENCE OF EXPLOSIVE ATMOSPHERE ZONE OF USE
1 Very high In the event of failure ofone means of protection, atleast an independent second means provides the requisite level of protection. Furthermore, the requisite level of protection is assured in the event of two faults occurring independently of each other. Equipment in this category must be so designed and constructed that sources of ignition do not becomeactive, even in the event of rare incidents relating to equipment. 1.0
1.1
1.2
1.3
1.4
1.5
1.6
2.1
Continuously or for long periods. 0
1
2
2 High The requisite level of protection is assured even in the event of frequently occurring disturbances or equipment operating faults which normally have to be taken into account. Equipment must be sodesigned and constructed as to prevent ignition sources arising, even in the event of frequently occurring disturbances or equipment operating faults which normally have to be taken into account. 1.0
1.1
1.2
1.3
1.4
1.5
1.6
2.2
Intermediate between previous and next condition. 1
2

21
22

3 High The requisite level of Protection is assured during normal operation. Equipment must be sodesigned and constructedas to prevent foreseeable ignition sources which can occur during normal operation. 1.0
1.1
1.2
1.3
1.4
1.5
1.6
2.3
If they do occur, theyare likely to do so onlyinfrequently and for a short period only. 2
22